banenr

product

Pid Gas Detector DT-AEC2531 Combustible Gas Monitoring Device for Underground Well Room – Action

Short Description:

ACTION gas detectors are OEM & ODM supported and true mature devices, long-tested in millions of projects domestic and overseas since 1998! Don't hesitant to leave your any inquiry here!


Product Detail

Product Tags

Related Video

Feedback (2)

Our growth depends around the superior machines, exceptional talents and consistently strengthened technology forces for Lel On Gas Monitor, fan linkage box, Medical Gas Pipeline System In Hospitals, You may find the lowest price here. Also you will get high quality products and excellent service here! Please do not hesitate to contact us!
Pid Gas Detector DT-AEC2531 Combustible Gas Monitoring Device for Underground Well Room – Action Detail:

Background

In the process of using natural gas, various equipment and devices such as pipelines, gate stations, pressure regulating equipment, valve wells, etc. are involved. These complicated gas supply equipment and pipe networks have brought many problems to the management of gas companies, especially the management of gas valve wells. Gas valve wells can cause gas leakage due to equipment aging, faults, and improper operation of personnel. However, traditional manual inspections are difficult to rush to the site for effective treatment in the first time due to the inspection density and inspection effect. All these have brought challenges to the management of gas companies.

Product advantages

1) Using advanced laser sensors (tunable laser spectroscopy (TDLAS) technology) with low false alarm and the service life is up to 5-10 years;

2) Adopt NB-IoT communication and cooperate with mainstream operators such as China mobile and telecommunications to ensure reliable communication;

3) The whole machine is designed with low power consumption and long working time, which can effectively reduce the equipment maintenance cost.

Main features

1) Large-capacity battery(152Ah) of domestic first-line brand, reliable capacity;

2) Using advanced laser sensors (tunable laser spectroscopy (TDLAS) technology, with high reliability, strong anti-interference ability, low false alarm rate and maintenance free;

3) Adopt NB-IOT wireless remote transmission solution, low power consumption, wide coverage and strong connection ability;

4) Well cover abnormal alarm and emergency treatment to prevent accidents;

5) The flooding alarm function detects the equipment status and informs the user that the equipment is in the detection empty window period.

Technical specifications

Performance

Detected gas

Combustible gas(Methane)

Detection principle

Tunable diode laser absorption spectroscopy technology(TDLAS)

Alarm error

±3%LEL

Detection range

0 ~ 100%LEL

Indication error

±3%LEL(Displayed on the access platform)

Alarm setting value

Low limit:25%LEL; High limit:50%LEL

Response time(T90)

T90≤10s

Wireless communication

NB-IoT

Detection interval

60minutes(Standard working mode)

Communication interval

24hour(Standard working mode)

Reporting time

08:00(Default)

Protection grage

IP67

Explosion proof grade

ExdibⅡCT4 Gb

Sensor storage life (under normal storage environment)

5 years

Sensor service life (typical)

5 years

 

Electrical characteristic

Power supply

Disposable lithium battery power supply(152Ah)

Operating voltage

3.6VDC

Battery operating hours (under standard operating mode)

≥3years

Continue working time after battery under voltage (under standard working mode)

15days

Environmental parameters

Environmental pressure

86kPa~106kPa

Environment humidity

≤100%RH(No condensation)

Environment temperature

-40℃~+70℃

Storage environment

Storage temperature: -20℃~+30℃, relative humidity ≤60%RH, no corrosive substances on site

Structure characteristics

Dimensions

545mm×205mm×110mm

Material

Cast aluminum

Weight

About 6kg(including battery)

Installation mode

Wall mounted: bracket hanging and fixing

Stability

100mm drop resistance (with packaging)

Boundary Dimension

Mounting Mode


6.1 Detector installation mode:
When detecting combustible gas with lower specific weight than air such as methane, the detector shall be installed as close to the wellhead as possible (the distance from the wellhead shall not be more than 30cm)

6.2 Manhole cover displacement switch installation method
The manhole cover displacement switch is perpendicular to the ground plane, and the top of the manhole cover displacement switch trigger rod is more than 2cm higher than the manhole cover (as shown in the figure below). After installation, the switch can be triggered when the manhole cover is closed.


Product detail pictures:

Pid Gas Detector DT-AEC2531 Combustible Gas Monitoring Device for Underground Well Room – Action detail pictures

Pid Gas Detector DT-AEC2531 Combustible Gas Monitoring Device for Underground Well Room – Action detail pictures


Related Product Guide:

We not only will try our greatest to offer you excellent services to each individual client, but also are ready to receive any suggestion offered by our buyers for Pid Gas Detector DT-AEC2531 Combustible Gas Monitoring Device for Underground Well Room – Action , The product will supply to all over the world, such as: Manchester, Mauritius, Frankfurt, We strongly believe that technology and service is our base today and quality will create our reliable walls of future. Only we have better and better quality , could we achieve our customers and ourselves, too. Welcome customers all over the word to contact us for getting further business and reliable relationships. We are always here working for your demands whenever you need.
The after-sale warranty service is timely and thoughtful, encounter problems can be resolved very quickly, we feel reliable and secure.
5 Stars By Irma from Bangkok - 2017.11.20 15:58
Reasonable price, good attitude of consultation, finally we achieve a win-win situation,a happy cooperation!
5 Stars By Belinda from Armenia - 2017.09.28 18:29
Write your message here and send it to us