  • ACTION gas detectors are OEM & ODM supported and true mature devices, long-tested in millions of projects domestic and overseas since 1998! Don't hesitant to leave your any inquiry here!


    Product Detail

    Product Tags

    Related Video

    Feedback (2)

    It really is a good way to further improve our goods and service. Our mission would be to acquire inventive items to buyers with a very good encounter for Combustible Gas Detector Working Principle, Pid Gas Detector, Medical Gas Alarm System, We've been honest and open up. We glance ahead on your pay a visit to and developing trustworthy and long-term standing relationship.
    Fixed Gas Detection System Regulation GT-AEC2338 Fixed Gas Detector – Action Detail:

    Technical Parameters

    Item

    Data

    Detected gases

    Combustible gases and steams, toxic and hazardous gases (see A01, A03 and B04~B29 in the list of detectable gases)

    Sampling mode

    Diffusive sampling

    Operating voltage

    DC24±6V

    Power consumption

    ≤3W (DC24V)

    Display

    LCD display

    Calibration

    By keys or a remote controller

    Signal transmission distance

    ≤1500m (2.5 mm2)

    Protection grade

    IP66

    Explosion proof grade

    ExdⅡCT6Gb

    Signal transmission

    Three-wire (4~20)mA standard signals [support HART] and 3 sets of relay signals

    Outlet hole connecting thread

    NPT3/4"(female)

    Material

    Cast aluminum

    Dimension

    Length × width × height: 228mm×177mm×87mm

    Weight

    1.9 kg

    Major Features

    Highly-integrated functional module design

    The integrated functional module is made up of two parts, i.e. detector module and sensor module. Anti-misplug standard digital interface is used between the two modules, good for on-site hot plug replacement;

    Alarm concentration can be set freely within the full range

    Low alarm concentration and high alarm concentration can be set freely within the full range. As keys are used for calibration, the calibrated value can be set according to calibrated gas concentration. Concentration is displayed through LCD on a real-time basis. On-site calibration can also be perfomed with an IR remote controller. At the time of calibration, it is unnecessary to open the cover. The operation is easy and convenient;

    Military-grade LCD display

    LCD real-time concentration display, clearly indicating equipment working conditions under highlight and in distance;

    Multiple communication modes are available

    Such product types as three-wire (4-20mA), two-wire (4-20mA), and 4-20mA with HART are available for selection;

    Flexible combination and multiple output modes

    Multiple detector modules and multiple types of sensor modules can be combined flexibly to form detectors with special output functions and applicable to different targets to meet customers’ customized demands;

    Replace a sensor as easy as replacing a bulb

    Sensor modules for different gases and ranges can be replaced freely. No calibration is required after replacement. That is, the detector can read ex-factory calibrated data and work immediately. In this way, the product has a longer service life. Meanwhile, detection calibration can be done easily at different sites, avoiding complicated dismantling process and difficult on-site calibration and reducing later maintenance cost.

    Model Selection

    Model

    Signal output

    Sensor equipped

    Adaptive control system

    AEC2338

    Three-wire (4~20)mA standard signal (supporting HART) and three sets of relay signals

    Two-wire (4~20)mA standard signal (supporting HART)

    Catalytic combustion, semiconductor, electrochemical, IR & PID

    ACTION gas alarm controllers:

    AEC2392a, AEC2392b, AEC2393a , AEC2393b2a-BS, AEC2393b2a-BM

    Detector Structure

    Boundary Dimension

    Material cast aluminum; Dimension: Length× width× height: 228mm×177mm×87mm Weight: 1.9 kg

    Mounting Mode

    Vertical pipe-mounted / Horizontal pipe-mounted / Wall-mounted / Ceiling-mounted


    Product detail pictures:

    Fixed Gas Detection System Regulation GT-AEC2338 Fixed Gas Detector – Action detail pictures

    Fixed Gas Detection System Regulation GT-AEC2338 Fixed Gas Detector – Action detail pictures

    Fixed Gas Detection System Regulation GT-AEC2338 Fixed Gas Detector – Action detail pictures


    Related Product Guide:

    Well-run equipment, professional sales team, and better after-sales services; We are also a unified big family, everyone stick to the company value "unification, dedication, tolerance" for Fixed Gas Detection System Regulation GT-AEC2338 Fixed Gas Detector – Action , The product will supply to all over the world, such as: India, Cairo, Ukraine, Our company upholds the spirit of "innovation, harmony, team work and sharing, trails, pragmatic progress". Give us a chance and we will prove our capability. With your kind help, we believe that we can create a bright future with you together.
    This company conforms to the market requirement and joins in the market competition by its high quality product, this is an enterprise that have Chinese spirit.
    5 Stars By Judy from Sacramento - 2018.08.12 12:27
    Sales manager is very enthusiastic and professional, gave us a great concessions and product quality is very good,thank you very much!
    5 Stars By Maria from Cape Town - 2018.09.29 13:24
    Write your message here and send it to us